AWWA C510-17(R21)

Current Reaffirmation
Double Check Valve Backflow Prevention Assembly

Best Price Guarantee Published: Jan 1, 2017 en - English 28 Pages

Sub Total (1 Item(s)) $ 0.00
Estimated Shipping $ 0.00
Total (Pre-Tax) $ 0.00
View in Library
or
American Water Works Association Logo

Double Check Valve Backflow Prevention Assembly

PUBLISH DATE 2017
This standard describes the double check-valve backflow prevention assembly for potable water applications. The assembly shall be capable of withstanding a working water pressure of at least 150 psi (1,034 kPa) without damage to working parts or impairment of function and for operation on hot or cold potable water lines. This standard describes hot- and cold-water double check-valve backflow prevention assemblies. Assemblies shall be designed to operate, at a minimum, at a temperature range of 33°F–140°F (1°C–60°C). Hot-water assemblies shall be designed to operate, at a minimum, in water at a temperature range of 33°F–180°F (1°C–82°C). A complete assembly consists of two internally loaded, independently operating check valves, located between two tightly closing resilient-seated shutoff valves, with four properly placed resilient-seated test cocks (see Sec. 4.3.1.3).