Standard Test Method for Fire Test of Non-Mechanical Fire Dampers Used in Vented Construction
1.1Â This fire-test-response standard assesses the ability of non-mechanical fire dampers used in vented construction in its open state to limit passage of hot gases, radiation, and flames during a prescribed fire test exposure. The fire exposure condition in this test method is sudden direct flame impingement, which produces these hot gases, radiation, and flames.
1.2Â This fire-test-response standard is intended to provide a means to assess the reaction of a non-mechanical fire damper used in vented construction to sudden direct flame impingement, or as a supplement to existing fire-resistive test methods, or both.
1.3Â This test method does not circumvent or eliminate the fire resistance rating requirements for construction. The fire resistance rating of construction shall be tested in accordance with published fire-resistance test standards as appropriate for the relevant application of the construction, or as required by the authority having jurisdiction (regulatory authority), or both. Non-mechanical fire dampers shall be tested to the appropriate fire-resistive test standards required for their application in order to determine a fire resistance rating in those constructions.
1.4Â This test method specifies the fire exposure conditions, fire test protocol, and criteria to evaluate an open state.
1.6Â This test method does not provide quantitative information about the test assembly related to the leakage of smoke, or gases, or both.
1.8Â This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.
1.9Â The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered requirements of this standard.
1.10Â The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
5.1Â This test method provides for the following observations, measurements and evaluations of an open state during the test fire.
5.2Â This test method does not provide the following:
5.2.1Â Evaluation of the degree to which the test assembly contributes to the fire hazard by generation of smoke, toxic gases, or other products of combustion.
5.2.2Â Measurement of the degree of control or limitation of the passage of smoke or products of combustion through the test specimen or the test assembly.